Back |
|
| |
|
PI -1 : Universal
Digital Process Indicator & Controller
Software calibration & range
setting
|
|
|
|
| |
|
|
| |
HIGHTLIGHTS |
|
| |
|
|
| |
 |
Non volatile RAM for storing calibration
configuration data |
 |
Two potential free relay outputs |
 |
Analog retransmission isolated output |
 |
Variable, user set hysteresis (dead band) |
 |
Internal 24VDC to power two wire transmitters |
 |
Software calibration, user accessible |
 |
Available in two front sizes : square 96
x 96, slim 96 x 48 |
|
|
| |
|
|
| |
Digital Process Indicator accurately displays
input type (as factory set) parameter value. It
alsoprovides two Alarm settings with two user
accessible potential free contacts and industry
standard, isolated, analog output.
With user accessible software calibration facility,
instrument can be calibrated at user's end.
PI-1, Universal Digital Process Indicator and
Controller
|
|
| |
|
|
| |
SPECIFICATIONS |
|
| |
|
Input Types
|
Factory set 4
Impedance
|
20 mA DC/ 0 20 mADC/RTD/mV/Thermocouple
100 Ohms for current inputs
|
|
Display
|
Range
Accuracy
Resolution
Type
|
0 100% of span, units as specified Display
+/- .25% of span
4 digits
Bright, 7-segment LED, red
|
|
Output
|
Analog
Accuracy
Load
Transmitter
|
4 20 mA DC , isolated
+/- .25% of span
upto 750 Ohms current inputs
24VDC, 25mA
|
|
Alarms
|
Contact Rating
|
two set points 230V AC, 5 A,
potential free |
|
Power
|
Consumption |
230VAC +/- 10%, 50Hz, (Optional 110 VAC)
< 3VA
|
|
Environmental
|
Temperature
Storage
Humidity
|
operating : 0 50 ° C
0 70 ° C
90% RH, NC
|
|
Mechanical
|
Dimensions
Weight
|
96 x 96 x 84 mm / 48 x 96 x 110 mm
540 gm
|
|
|
| |
|
|
|
|
|
|
|
 |
| |
|
|
Copyright © 2007 by Audiolec Instruments.